Intrinsically
safe
detectors
are used in
hazardous
locations
where
explosive
levels of
gas or
vapors are
normally or
potentially
present. The
SS-T-IS
circuit
power levels
are limited
to eliminate
the
potential to
ignite an
explosive
atmosphere.
Compatibility
of
intrinsically
safe
detectors
with the
system
control
panels for
ground fault
detection
and proper
use is
required.
Consult the
appropriate
listing
agency for
further
information
about the
use of
intrinsically
safe
products. An
approved
compatible
barrier must
also be used
in all
intrinsically
safe
applications
and can be
purchased
separately.
The model
SS-T-IS
intrinsically
safe
rate-of-rise
thermal
detector
with fixed
temperature
alarm set
point of
57°C uses a
state-of-the-art
dual
thermistor
sensing
circuit.
These
detectors
are designed
to provide
open area
protection
and are to
be used with
compatible
control
panels only.
Each
detector is
equipped
with two
LEDs that
provide 360°
visual
indication
of detector
status.
Remote LED
annunciator
capability
is also
included.
When the
temperature
at the
detector
exceeds
57°C, it
latches in
alarm and
remains in
this
condition
until it is
reset by a
momentary
power
interruption.
The detector
can be
tested by
activating
an internal
reed switch
with a test
magnet.