ALARM ACCEPT MODULE

Data Sheet   Product Approvals

Features

  • LED indication

  • 159 per loop

  • Easy to install

  • Rotary wheel for ease of addressing

  • Loop powered

  • Ideal for SOU applications

 

 

 

Description

The Alarm Accept Module (AAM) is can be used wherever fire brigade or engineered solutions allow use to assist in reducing false alarm calls to brigade.

Operation:
Each AAM is installed within the self occupied unit (SOU) together with a non-latching addressable detector with an addressable sounder base fitted.

When the smoke detector is activated, the addressable sounder in the room is also activated.
The occupant then has an Alarm Acknowledgement Period (nominally 30s) to press the button on the AAM to prevent transmission of the alarm to the fire brigade. Failure to do so will cause the alarm to transmit immediately.

Pressing the button on the AAM will give the occupant an Alarm Investigation Period (up to 180s) to clear the cause of the alarm and therefore return the system to normal state. Failure to clear the alarm within this period will cause the alarm to transmit immediately